Server Side Map Descriptors 
6.6.1. 
SlotServer Specific Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Map_Descriptor_Name 
Name 
of 
this 
Map 
Descriptor 
Up  to  32  alphanumeric 
characters 
Scan_Interval 
Rate  at  which  IO  image 
data is updated 
Use  twice  the  rate  used  in 
RSLogix e.g. 0.2s 
Function 
Function  of  Server  Map 
Descriptor 
WRBC  -  to  write  into  Input 
Image Data buffer 
 
RDBC - to read from Output 
Image Data buffer 
6.6.2. 
Driver Specific Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name of Node to fetch data 
from 
One  of  the  node  names 
specified  in  “Client  Node 
Descriptor” above 
IO_Data_Type 
Data type of IO image 
Use  same  as  used  in 
RSLogix to add the module 
INT               (16-bit integer) 
SINT             (8-bit signed) 
DINT             (32-bit double) 
REAL            (32-bit float) 
DA_Name_Start
2
 
Name  of  Data  Array  to 
include in IO image data 
One  of  the  Data  Array 
names  from  “Data  Array” 
section  above.  Data  Arrays 
must be named as follows: 
DaName_x      where  x  is  a 
value e.g. DaName_1 
DA_Count 
Number  of  Data  Arrays  to 
include in IO image data 
1-200 
Protocol_Type_ID 
Custom Value transferred in 
IO 
image 
to 
indicate  
protocol of IO image data 
0  -  value  permitted  by 
IO_Data_Type
3
 
e.g. 0 - 65535 for INT 
 
                                                 
2
 
Refer to Appendix A.6 for information specific to naming Logics driver Data Arrays.
 
3
 T
he  update  rate  decreases  as  the  number  of  blocks  go  up.  For  25  blocks  we  have  an  update  rate  of 
25*RPI = 25*0.1 = 2.5 seconds.