DANGER
  Do not attempt to activate the transfer switch 
manually until all power voltage supplies 
to the switch have been positively turned off. 
Failure to turn off all power voltage supplies 
may result in extremely hazardous and possibly 
fatal electrical shock.
5.  Use the manual transfer handle inside the trans-
fer switch to move the main contacts back to their 
“Utility” position, i.e., loads connected to the util-
ity power source (Figure 3.2).
6.  Turn ON the utility power supply to the transfer 
switch using the means provided.
7.  Set the system to automatic operation as outlined 
in “Automatic Transfer Operation,” Section 3.3.
3.6  SETTING THE EXERCISE TIMER
The  generator  is  equipped  with  an  exercise  timer. 
Once  it  is  set,  the  generator  will  start  and  exercise 
once every seven days, on the day of the week and at 
the time of day the following sequence is completed. 
During this exercise period, the unit runs for approx-
imately 12 minutes and then shuts down. Transfer of 
loads to the generator output does not occur during 
the exercise cycle.
A switch on the control panel (see Figure 3.1) allows 
for selection of the day and time for system exercise. 
To select the desired day and time of day, the follow-
ing sequence must be done at that time.
1.  Verify that the AUTO/OFF/MANUAL switch is set 
to AUTO.
2.  Hold down the set timer switch until the genera-
tor  starts  (approximately  10  seconds)  and  then 
release.
3.  The generator will start and run for approximately 
12 minutes and then shut down on its own. The 
exerciser will then be set to run at that time of day 
every week.
NOTE:
The  exerciser  will  only  work  in  the  AUTO  mode 
and  will  not  work  unless  this  procedure  is  per-
formed. The exerciser will need to be reset every 
time the 12-volt battery is disconnected and then 
reconnected.  The  exerciser  WILL  NOT  work  if 
dip switch 2 (Remote Not Auto) on the controller 
printed circuit board is ON.
3.7  PROTECTION SYSTEMS
3.7.1  LOW OIL PRESSURE SWITCH
This  switch  (Figure  3.3)  has  normally  closed  con-
tacts that are held open by engine oil pressure during 
cranking  and  operating.  Should  oil  pressure  drop 
below the 8 psi range, switch contacts close, and the 
engine shuts down. The unit should not be restarted 
until oil is added, and the AUTO/OFF/MANUAL switch 
must be turned to OFF and then back to AUTO.
3.7.2  HIGH TEMPERATURE SWITCH
This  switch’s  contacts  (Figure  3.3)  close  if  the  tem-
perature should exceed approximately 140º C (284º 
F), initiating an engine shutdown. The generator will 
automatically restart and the LED will reset once the 
temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and 
High Temperature Switches
Oil Filter
Oil
Drain
Hose
Low Oil Switch
High Temp Switch
Loosen
3.7.3  OVERCRANK
This  feature  prevents  the  generator  from  damaging 
itself when it continually attempts to start and anoth-
er problem, such as no fuel supply, prevents it from 
starting. The unit will crank and rest for a preset time 
limit.  Then,  it  will  stop  cranking,  and  the  LED  will 
light indicating an overcrank failure. The AUTO/OFF/
MANUAL switch will need to be set to OFF and then 
back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature 
will continue to activate.
Section 3 — Operation
Air-cooled 7 kW, 12 kW and 15 kW Generators