3.7.3.1   Approximate Crank Cycle Times
•  15 seconds ON
•  7 seconds OFF
•  7 seconds ON
•  7 seconds OFF
•  Repeat for 45 seconds
  Approximately 90 seconds total
3.7.4  OVERSPEED
This feature protects the generator from damage by 
shutting it down if it happens to run faster than the 
preset  limit.  This  protection  also  prevents  the  gen-
erator  from  supplying  an  output  that  could  poten-
tially damage appliances connected to the generator 
circuit. Contact the nearest Authorized Dealer if this 
failure occurs.
4.1  FUSE
The  generator  panel’s  15  amp  fuse  (Figure  4.1)  pro-
tects the DC control circuit against overload. The fuse 
is  wired  in  series  with  the  battery  output  lead  to  the 
panel. If the fuse element has melted open, the engine 
cannot crank or start. Replace the fuse using only an 
identical 15-amp replacement.
The generator panel’s 5 amp fuse protects the battery 
charge circuit against overload. If the fuse element has 
melted  open,  battery  charging  will  not  be  possible. 
Replace the fuse using only an identical 5 amp replace-
ment. To remove fuse, push cap down and rotate coun-
terclockwise.
Figure 4.1 – Generator Control Panel
HIGH TEMP.
OVER SPEED
LOW OIL
SYSTEM SET
OVER CRANK
MAN.
SET
OFF
AUTO
15A
FUSE
EXERCISE
TIME
R
POWER SYSTEMS, INC.
L o c a t e y o u r n e a r e s t
d e a le r a t :
R
FUSE
5A
E X E R C IS E R N O T S E T
N O U T IL IT Y S E N S E
4 F L A S H IN G R E D L E D S =
F L A S H IN G G R E E N L E D =
4.2   CHECKING THE ENGINE
OIL LEVEL
For  oil  capacities,  see  “Specifications,”  Section  1.5. 
For  engine  oil  recommendations,  see  Section  4.3.1. 
To  check  the  engine  oil  level,  proceed  as  follows 
(Figure 4.2):
1.  Start  the  generator  by  moving  the  Auto/Off/
Manual switch to the MANUAL position. Allow it 
to run for a short while and then shut it down by 
moving the switch to the OFF position.
2.  Remove  the  dipstick  and  wipe  it  dry  with  a
clean cloth.
3.  Install the dipstick; then, remove it again. The oil 
level should be at the dipstick “Full” mark. If nec-
essary, add oil to the “Full” mark only. DO NOT 
FILL ABOVE THE “FULL” MARK.
  Never operate the engine with the oil level 
below the “Add” mark on the dipstick. Doing 
this could damage the engine.
4.  Install the dipstick.
5.  Reset the AUTO/OFF/MANUAL switch to its origi-
nal position.
Figure 4.2 — Oil Dipstick and Fill, 7 kW
Oil Dipstick and Fill
Figure 4.3 — Oil Dipstick and Fill, 
12 kW and 15 kW
Oil Dipstick
Oil Fill
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators