Installation and operating Instructions 
Xtender V1.3 
Page 30 
 
13
  Figure element's (AC part) 
Elem.
 
Description
 
Comment
 
Input supply cable  The section is determined by means of the maximum current at 
source and the protection device (H). In multi-unit systems, cables (A) 
of the same phase must have the same length and section (see 
comment fig. 12-2/3).  
 
B Output supply 
cable 
In multi-unit systems, cables (B) of the same phase must have the 
same length and section (see comment fig. 12-2/3). The section must 
be selected by means of the Xtender’s output current given on the 
type plate and the protection device selected for the input (see fig. 
1a). 
Connection of the 
neutrals 
See chapter 4.2 - p. 10.  
In a fixed installation where the neutral is connected to the earth at a 
single installation point upstream of the Xtender, it is permissible to 
carry out a connection of the neutrals in order to preserve an 
unchanged earthing system downstream, independent of the 
operating mode of the Xtender. This choice shows the advantage of 
keeping the differential protection devices downstream of the 
Xtender.  
This connection (C) is not permitted if a socket is installed upstream 
of the Xtender. 
D Differential 
circuit 
breaker 
A protection device must be installed downstream of he source (G or 
U) according to the local requirements and in compliance with the 
applicable regulations and standards.  
E Earth-neutral 
connection bridge 
The neutral is earthed at a single point of the installation, downstream 
of the source and upstream of the protection device(s) at the default 
current (DDR). When several sources are available, each source must 
have an earthed neutral. If the source has to be retained with an 
isolated earthing system (IT) the applicable local provisions and 
regulations must be applied. 
F AC 
output 
protection devices 
for the Xtender 
A protection device dimensioned in dependence of the cable section 
used may be installed downstream of the Xtender (main circuit 
breaker before distribution). The cable section is to be dimensioned 
according to the calculation table of maximum output current (fig. 1). 
The Xtender has an internal current limitation the value of which is 
stated on the type plate Fig. 1b (35). 
Generator 
The generator is dimensioned according to the requirements of the 
user. Its rated current will determine the configuration adjustment 
{1107} “maximum current of the AC source”.  
H Protection 
devices 
at the Xtender 
input 
The protection device at the input of the Xtender must be 
dimensioned according to the power output of the source at the 
cable section used. It will not exceed a calibre equivalent to the input 
current “I AC in” given on the type plate of the unit Fig. 1b (35). 
J  
 
K Connection 
plug 
socket 
If the Xtender is connected to an AC source by means of a plug, the 
connection cable must not exceed a length of 2 m, and the socket 
must remain permanently accessible. The socket will be protected by 
a protection device of appropriate calibre. The connection of the 
neutrals (C) is prohibited in this case. 
L  
 
P  
 
R  
 
Secured grid 
Distribution to the users supplied by the grid or the generator when 
this is present or by the Xtender within the limit of its power output 
from energy stored in the battery. This distribution is carried out in 
conformity with the local standards and regulations.