Studer Innotec XTH 8000-48 Manual Do Utilizador

Página de 36
STUDER Innotec 
Xtender 
Installation and operating Instructions 
Xtender V1.3 
Page 31 
 
Elem.
 
Description
 
Comment
 
Non-secured grid 
Distribution to users supplied exclusively via the present grid or the 
generator. 
This distribution is carried out in conformity with the local standards 
and regulations.  
Public grid 
The connection to the public grid imposes adherence to the local 
standards and regulations at the responsibility of the installer. The 
installation should, in principle, be checked and approved by an 
official body. 
V Automatic 
earth-
neutral connection 
This connection is deactivated by default. In may be used in certain 
specific cases for automatically re-establishing the neutral system 
type TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode. 
The activation is carried out via RCC-02/03 remote control 
configuration {1485}. This operation may only be carried out by 
qualified personnel, under the responsibility of these personnel, and in 
conformity with the local standards and regulations. See 4.2.3– p.11 
Galvanic 
isolator 
This device (optional) is generally used to reduce the risk of 
electrolytic corrosion due to the direct current when a boat is 
connected at the dock.   
X Source 
reversing 
switch 
When the installation has more than one supply source, it is 
necessary to install a switching device between the sources, 
simultaneously switching the neutral and the phase(s) of these 
sources. In all cases this device (manual or automatic) must 
guarantee interruption of the connected source before its connection 
to another source. 
Y Isolation 
transformer 
This device (optional) prevents the risk of galvanic corrosion due to 
direct currents when a boat is connected at the dock. 
 
 
 
14
  Elements of connexion cabinet (Fig 4a) 
Pos.
 
Denomination
 
Description
 
Comment
 
1 ON/OFF 
 
Main switch 
Main on/off switch 
See chapter 7.1 - p 24. 
2  Temp. 
Sens  Connector for the battery 
temperature sensor 
See chapter 6.4.2 – p. 24. 
Only connect the original Studer BTS-01 
sensor  
Com. 
Bus Double connector for 
connecting peripherals such as 
the RCC002/03 or other 
Xtender units 
O / T 
(Open / 
Terminated) 
Switch for terminating the 
communication bus. 
See chapter 4.5.9 – p. 14. 
The two termination switches (4) for the 
communication bus both remain in 
position T (terminated) except when both 
connectors are in use. 
-- 
3.3 V (CR-2032) lithium ion type 
battery socket 
Used as a permanent supply for the 
internal clock. See chapter 6.2.11 - p 21. 
-- 
Jumper for programming the 
off/on switch by dry contact 
See chapter 6.2.12 – p. 21 and fig. 8b 
point (6) and (7). They are positioned at A-
1/2 and B-2/3 by default 
7 REMOTE 
ON/OFF 
Connection terminals for dry 
on/off remote connection. 
See chapter 6.2.12– p. 21).  
When the control via dry contact is not 
being used, a bridge must be present 
between the two terminals. 
8 AUXILIARY 
CONTACT 
Auxiliary contact 
 (See chapter 6.2.10– p. 21) 
Take care not to exceed the admissible 
loads  
-- 
Activation indicators for auxiliary 
contacts 1 and 2 
See chapter 6.2.10– p. 21