Entry description:
Access Read/write
PDO mapping
No
Value range
INTEGER16
Default value
0
Note: The value in 6073h (which is in mA) is entered in PL[1] after it is converted to
Amperes. For example:
If we want PL[1] to be 4 Amps,
and in [0x6075] is set to 3200 mA
then [0x6073] = 4000 * 1000 / 3200 = 1250
Object 0x6074: Torque Demand value
This value represents the maximum permissible torque creating current in the motor
and is given in units of per thousand of rated current.
and is given in units of per thousand of rated current.
Object description:
Index 6074h
Name Max
current
Object code
VAR
Data type
INTEGER16
Category Mandatory
Entry description:
Access Read
PDO mapping
No
Value range
INTEGER16
Default value
0
Note: This Object reflects DV[1]
CANopen DSP 402 Implementation Guide
MAN-CAN402IG (Ver. 1.2)
105