ETR-PT (Enhanced Tone Receiver Port)
Issue 1 June 2005
1171
 
1002
ABRT
The system could not allocate time slots for the test connection. This 
situation could occur when the system is heavily loaded. If the system 
is not heavily loaded, test the TDM-BUS with test tdm.
1. Retry the command at 1-minute intervals up to 5 times.
1003
ABRT
The system could not allocate a Tone-Clock for the test connection. 
This may be caused by a heavy load on the system or by a faulted 
Tone-Clock.
1. Check to see if there are any alarms against the TONE-BD or 
TONE-PT in the PN where the test aborted.
2. If a new Tone-Clock has been inserted, allow about 1 minute for 
maintenance to run on the newly inserted circuit pack.
3. Retry the command at 1-minute intervals up to 5 times.
2000
ABRT
Circuit pack’s response to the test request was not received within the 
allowable time period.
1. Retry the command at 1-minute intervals up to 5 times.
2006
ABRT
This abort code indicates that the active Tone-Clock circuit pack or a 
Tone Detector circuit pack may not be functioning properly.
1. Test the active Tone-Clock circuit pack in the PN with test 
tone-clock UUC.
2. Retry the command at 1-minute intervals up to 5 times.
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1–122
FAIL
DTMF digits were not detected correctly.
1. Run the short test sequence with test port location sh r 
1.
2. If the problem persists, the system is still operating properly but 
capacity is reduced. To restore performance to normal, replace the 
circuit pack with the defective ETR-PT.
Table 403: Test #42 Tone Detection Verification Test  (continued)
Error 
Code
Test 
Result
Description / Recommendation
 2 of 3