Avaya 03-300430 User Manual
Communication Manager Maintenance-Object Repair Procedures
1288 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
For EI-to-EI fiber links, this test is not run. For EI-to-SNI fiber links, this test is run on the SNI
circuit pack endpoint of the fiber link. For SNI-to-SNI fiber links, this test is run on both SNI
circuit pack endpoints of the fiber link.
circuit pack endpoint of the fiber link. For SNI-to-SNI fiber links, this test is run on both SNI
circuit pack endpoints of the fiber link.
Table 442: Test #777 Failure Audit
Error
Code
Code
Test
Result
Result
Description / Recommendation
2100
ABRT
Could not allocate the necessary system resources to run this test.
2300
ABRT
The downlink message necessary to run this test could not be sent.
2301
ABRT
The software timer could not be set before sending the downlink message
necessary to run this test.
2302
ABRT
The SNI circuit pack claims that it received a bad message from software.
2303
ABRT
The SNI circuit pack claims that the test requested by software is invalid.
2304
ABRT
SNI firmware is not able to run the test.
1. Retry the command at 1-minute intervals up to 3 times.
2306
ABRT
An SNI circuit pack on the fiber link is not responding to test requests sent
by software.
by software.
1. Run the test led switch-node for the switch node(s) where the
SNI(s) reside to verify whether the LEDs on the board(s) light. Follow
the steps below for the SNI(s) from step 1 that had no LEDs light.
the steps below for the SNI(s) from step 1 that had no LEDs light.
2. If the LEDs on the other boards in the carrier light, but the LEDs on this
board do not light, run test 760 via test board location l for the
active SNC in this carrier. Wait 5 minutes and then try step 1 one more
time. If the LEDs on this board still do not light, replace this board.
(Replacing an SNI may be service interrupting. Refer to the SNI-BD
section for the procedure to replace an SNI.)
time. If the LEDs on this board still do not light, replace this board.
(Replacing an SNI may be service interrupting. Refer to the SNI-BD
section for the procedure to replace an SNI.)
3. If none of the LEDs light for the boards in the same carrier as this board,
fix any problems associated with the connectivity of this carrier to the
media server. Use list fiber-link to determine the fiber
media server. Use list fiber-link to determine the fiber
connections to this carrier. Check the LEDs on every SNI and EI, and fix
any fiber problems. Enter display errors and resolve any
any fiber problems. Enter display errors and resolve any
EXP-INTF error entries associated with the Port Network. Also, resolve
any SYNC, SNI-BD, SNC-BD, FIBER-LK, or SNI-PEER error entries.
any SYNC, SNI-BD, SNC-BD, FIBER-LK, or SNI-PEER error entries.