22
REMOTE OPTIONS
If an alarm occurs during a remote connect, the panel disconnects from the
service receiver and connects to the alarm receiver. Alarm reports are only sent
to the alarm receiver. It is important that the alarm receiver key and the service
receiver key programmed at the central station are NOT the same so the panel can
determine the difference between receivers.
When NO is selected, remote commands and programming are not accepted from a
When NO is selected, remote commands and programming are not accepted from a
secondary service receiver.
26.6
Remote Disarm
Enter YES to enable the panel to be disarmed remotely. Selecting NO disables
remote disarming. Default is YES.
26.7
App Key
Enter the 8-digit App Key obtained in your Dealer Settings tab at
dealeradmin.securecomwireless.com.
This option is a security feature of the Virtual Keypad iPhone/Android App used
This option is a security feature of the Virtual Keypad iPhone/Android App used
only when your Dealer Settings at dealeradmin.securecomwireless.com have
“EASYconnect” set as the Communication Type.
This communication option is used to eliminate the need for a static IP address
This communication option is used to eliminate the need for a static IP address
programmed in Network Options.
To enter the App Key, press any select key and enter any combination
To enter the App Key, press any select key and enter any combination
of 8 digits.
Press COMMAND. The default for this option is blank.
Press COMMAND. The default for this option is blank.
System Reports
27.1
System Reports
This function allows you to select the reports the XTLplus sends to the receiver.
27.2
Opening/Closing Reports
NO - No Opening/Closing Reports are sent.
YES - Sends Opening/Closing Reports for each programmed area.
27.3
Abort Reports
YES allows the panel to send an Alarm Abort Report to the receiver any time an
area is disarmed during Transmit Delay before an alarm report is sent and the
Bell Cutoff Time has not expired. See the Bell Cutoff section. The area must be
disarmed and no zones that were in alarm can still be armed.
YES also allows a Bell Silenced Report to be sent if the alarm bell is silenced with a
valid user code during an alarm. Default is NO.
Note: Alarm Cancel or Verify Reports are sent if the alarm is canceled or verified
after being sent to the alarm receiver, if the Bell Cutoff timer has not expired. The
Abort Reports option does not affect Cancel or Verify reports.
The panel will not send Abort reports for Fire zones, or Supervisory-type zones.
27.4
Zone Restoral Reports
This option allows you to specify whether the panel sends zone restoral reports and
when they will be sent.
NO - Restoral reports are not sent by the panel.
YES - The panel always sends zone restoral reports at the time the zone restores
from an alarm or trouble condition.
DISARM - The panel sends zone restoral reports when a zone that has restored
from an alarm or trouble is disarmed. Twenty-four hour zones send
restorals immediately.
27.5
Bypass Reports
YES allows the panel to send all zone bypass, reset, and force arm reports to the
receiver. The bypass report includes the zone number, zone name, and the user
number of the individual bypassing the zone.
27.6
Code Change Reports
YES allows the panel to send all code additions, changes, and deletions to the
receiver. The code change report includes the user number added or deleted and
the user number of the individual making the change.
DISARM
NO YES
APP KEY:
SYSTEM REPORTS
SYSTEM REPORTS
O/C RPTS NO YES
ABORT
NO YES
RESTORAL YES
NO YES DISARM
NO YES DISARM
BYPASS
NO YES
CODE CHG NO YES