XTLplus Installation and Programming Guide
24
SYSTEM OPTIONS
Exit Delay timer restarts. This restart can occur only once.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end 
of the exit delay then one of two sequences occur:
For Entry Delay 1 EX type zones:
• The bell sounds for the length of time set in Bell Cutoff programming
• The Entry Delay operation starts, requiring code entry to disarm
• If not disarmed, a zone alarm and an Exit Error are sent to the receiver
For Entry Delay 2 EX type zones:
• The zone is force armed and a zone force arm message is sent to the receiver
• An Exit Error is sent to the receiver
• The bell sounds for the length of time set in Bell Cutoff programming
28.7 
Cross Zone Time
Enter the time allowed between zone faults. When a zone programmed for cross 
zoning faults, the panel begins counting down the Cross-Zone Time entered here. If 
the same zone or another cross-zoned zone faults within this time, an alarm report 
is sent to the receiver.
If the Cross-Zone Time expires without the second zone fault, only a zone fault 
report from the first zone is sent to the receiver. The Cross-Zone Time can be from 
4 to 250 seconds in one second increments. Enter 0 (zero) to disable the Cross-
Zone Time feature. Default is 0 (zero). See the Appendix.
28.8 
Power Fail Delay
This option tracks the duration of an AC power failure. The delay time can be from 
1 to 9 hours. When the AC power is off for the length of the programmed delay 
time, an AC power failure report is sent to the receiver. For example, if the power 
failure delay is set for two hours, then the AC power failure report will be sent 
between 2-3 hours. Entering a 0 (zero) sends the AC power failure report within 15 
seconds. Default is 1.
28.9 
Swinger Bypass Trips
Enter the number of times (1-6) a zone can go into an alarm or trouble condition 
within one hour be fore being auto matically bypassed. Bypassed zones are auto-
matically reset when the area they are assigned to is disarmed. All 24-hour zones 
are reset when any area of the system is dis armed. A programming Stop operation 
restores a bypassed zone. Entering 0 (zero) disables this function. Default is 2.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires 
before the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip 
counter is exceeded before the hour expires, the zone is auto matically bypassed 
by the panel. A Bypass Re port is sent to the receiver if Bypass Re ports is YES.
Note: Not investigated by Intertek.
28.10 
Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in 
a normal condition for one complete hour after being bypassed. A report of the 
automatic reset is sent to the receiver if Bypass Reports has been se lected as YES. 
Default is NO.
Note: Not investigated by Intertek.
28.11 
Zone Activity Hours
This option provides supervision of a person living alone for non-activity. Enter the 
number of hours, 0 to 9, allowed to elapse without a disarmed zone being tripped 
before a message is sent to the receiver. Default is 0 (zero).
When the system is disarmed, the timer begins to countdown the number of hours 
programmed. Each time activity occurs, the timer restarts the countdown. 
Before the countdown time expires, the keypad sounds a tone and PRESS ANY KEY 
displays to allow the user to restart the activity timer. The duration of the tone is 
the number of seconds programmed for Entry Delay 2.
Select the SUPV/TRBL receiver option in communication programming to send S93 
ALARM: User Activity Not Detected, S94 Alert: Activity Check Enabled, and S95 
Alert: Activity Check Disabled messages.
When an open/close schedule is programmed, the timer only counts down during 
the scheduled open period. Also, when a schedule is programmed, if the timer is 
counting down and the scheduled open time occurs, the timer resets and begins 
the countdown again.
CRS ZONE TM:
0
PWR FAIL HRS:
1
SWGRBYPS TRIPS:  2
RST SBYP  NO YES
ZN ACTY HRS:
0