SYSTEM REPORTS
27.7 Ambush
YES allows an ambush report to be sent any time user code number one is entered 
at a keypad. Selecting NO disables the ambush report and allows user code number 
one to operate the same as all other codes.
27.8 
Late To Open
Enter 1-240 as the number of minutes to elapse that the system may remain armed 
after the opening time of a schedule without sending a Late To Open message. If 
the system continues to be armed after the Late to Open minutes expire, a Late To 
Open message is sent to the central station. Default is 0, which disables the Late 
To Open option.
27.9 
Early To Close
Enter 1-240 as the number of minutes that the system can be armed prior to the 
scheduled closing time. If the system is armed prior to the Early to Close minutes, 
an Early To Close message is sent to the central station. Default is 0, which 
disables the Early to Close option.
System Options
28.1 
System Options
This section allows you to select system wide parameters used in the operation of 
the XTLplus panel. A description of each System Option follows:
28.2 System
This configures the panel as either a six Area system, an All/Perimeter system 
(Perimeter/Interior), or a Home/Away system (Perimeter, Interior, and Bedrooms). 
Zones must be assigned to Bedrooms for the area to be active.
Wireless zones in an Area or All/Perimeter system resound the trouble buzzer every 
four hours when zone trouble or low battery is displayed.
28.3 
Closing Code
When YES is selected, a code number is required for system arming. If NO is 
selected, a code number is not required for system arming. Default is NO.
28.4 
Closing Check
Select YES to enable the panel to verify that all areas have been armed after a 
schedule expires. If the Closing Check finds any areas disarmed past the scheduled 
time, all keypads emit a steady beep and display CLOSING TIME!. The user must 
extend the schedule or arm the system within 10 minutes or a Late to Close 
message is sent to the central station. Default is NO.
28.5 
Entry Delay 1
Enter the entry delay time for all exit type zones programmed to use Entry Delay 
1. When an armed Exit type zone is faulted, the keypad prewarn tone begins 
sounding. ENTER CODE: - and the name of the zone causing the Entry Delay 
displays on all keypads.
When the first digit of a code is entered, the prewarn tone stops at the keypad. 
If, within five seconds, a valid user code is not entered or an invalid user code is 
entered, the prewarn tone begins sounding again. Fifteen seconds must elapse 
before entering a digit silences the prewarn tone again.
The area must be disarmed before the entry delay expires or an alarm is detected. 
All Burglary type zones in all areas are delayed along with the Exit zone.
Entry delay times can be from 30 to 250 seconds. Repeat the above for Entry Delay 
2 if it is being used. Default is 30 seconds for Entry Delay 1.
Note: Specific Exit Error operation is based on the Entry Delay used (1 or 2) with an 
EX type zone. See Exit Delay.
28.6 
Exit Delay
Enter the Exit Delay time for all Exit type zones. When the exit delay time starts, 
all activity on exit and burglary zones is ig nored until the exit delay expires. The 
keypad displays the Exit Delay time countdown and annunciates the Exit Delay 
tone at 8 second intervals until the last 10 seconds when annunciation is at 3 
second intervals. The exit de lay can be from 45 to 250 sec onds. Default is 60 
seconds. During Exit Delay, if an exit zone trips, then restores, and trips again, the 
AMBUSH  NO YES
LATE TO OPEN
MINUTES:  
0
EARLY TO CLOSE
MINUTES:  
0
SYSTEM OPTIONS
SYSTEM OPTIONS
SYSTEM: ALL/PERIM
AREA  A/P   H/A
CLS CODE  NO YES
CLS CHK  NO YES
ENTRY DLY 1:
30
ENTRY DLY 2:
60
EXIT DELAY:  
60