Emerson AE4-1395 Manuel D’Utilisation

Page de 19
9
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE4-1395
Application Engineering
B
U
L
L
E
T
I
N
7.  Using the appropriate lifting devices, carefully 
remove the compressor from the system.
The following steps should be followed to install the digital 
compressor into the system.
1.  Before removing the rubber plugs, install the 
compressor in the unit on the mounting grommets 
using the appropriate lifting devices.
2.  Install the compressor mounting bolts.
3.  Connect the suction and discharge lines using 
standard brazing practices.
4.  If the compressor has an external modulation valve 
and tubing (3 to 7.5 ton only) refer to 
Figure 8 for the 
correct valve orientation and position. Wrap a wet 
rag around the valve and complete the assembly 
by brazing the valve and tubing into place.
5.  Check for leaks using nitrogen with a properly sized 
regulating and relief valve.
6.  Connect conduits and wiring to the compressor. 
Inspect and/or replace the contactor. If the 
compressor is 1-phase, install the correct run 
capacitor.
NOTICE
The above procedures for changing the 
compressor are not comprehensive and additional 
steps/procedures may be necessary.
Refrigerant Flow Control
In the system with a digital compressor, the refrigerant 
flow control valve is required to control flow across a wide
range of flow rates and varying pressure differentials.
Most balanced port thermostatic expansion valves can 
control flow down to about 40% of their rated capacity.
Excessive hunting and loss of superheat control can 
result when asking a thermostatic expansion valve to 
operate outside of its design range. For this reason, 
the expansion device needs to be evaluated to ensure 
reliable operation over the expected operating range. 
Limiting the minimum compressor modulation rate to 
a value that the expansion valve can tolerate should 
be considered. Electronic expansion valves should be 
considered if modulation over the entire range of the 
compressor’s modulation range is anticipated.
Evaporator Air Flow
For the highest level of energy savings, comfort, and 
efficiency the variable capacity system should be capable
of  varying  the  air  flow.  Variable  frequency  drives  and
tapped  blowers  are  two  means  of  reducing  air  flow.
Reducing  air  flow  in  humid  or  maritime  climates  is
important to maintain coil temperatures low enough to 
remove latent heat. In desert and arid climates, because 
of low or no latent loads, air flow is less critical.
The controls required for variable air flow are not provided
by Emerson so the contractor may need to consult with 
controls experts in this field.
Condenser Air Flow
Modulating the condenser air flow is not critical to the
success of the application. For the highest level of energy 
savings, condenser air flow will be reduced based on the
compressor modulation rate, condensing temperature, 
ambient temperature, etc.
Modulation Control
The preferred modulation control for retrofit applications
is the Commercial Comfort Controller. This controller is a 
closed loop controller that is installed in the conditioned 
space. The controller measures the space temperature 
and through an algorithm in the controller, controls the 
modulation of the digital scroll. The controller can be 
positioned up to 300 feet from the compressor/unit, is 
configurable for roof top unit or heat pump, and is wired
like a commercial room thermostat. For more information 
on the Commercial Comfort Controller please refer to 
AE8-1393.
 
ASSEMBLY LINE PROCEDURES
3 To 7.5 Ton Modulation Valve Brazing Procedure
The external modulation valve is purchased and shipped 
separately from the 3 to 7.5 ton digital scroll. Therefore, 
assembly is required in the OEM manufacturing plant. 
Figure 8 illustrates the correct position and orientation 
of the modulation valve. Please note the direction of the 
arrow on the valve, it must point to suction.
When brazing the modulation valve into the system, 
the valve must be wrapped with a wet rag to help keep 
the valve cool. The torch flame must be directed away
from the valve and the brazing operation should be 
done quickly so the valve isn't overheated. The brazing 
operation should be performed with a nitrogen purge to 
prevent the build-up of copper oxide. The solenoid coil 
should be installed after the brazing operation, so the 
leads are kept away from the brazing operation and the 
wet rag is able to fully contact the valve body.
Pressure Testing
The pressure used on the OEM assembly line to meet 
the UL burst pressure requirement cannot be higher 
than
 400 psig (27.6 bar) for R-407C & R-22 and 475 
psig (32.8 bar) for R-410A. Higher pressure may result 
in permanent deformation of the compressor shell and 
possibly cause misalignment or bottom cover distortion.