Honeywell International Inc. WFSRM Manuale Utente

Pagina di 68
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C  5/8/2015
19
Configuration and Programming
FWSG FlashScan Wireless System Gateway
in their final mounting locations prior to initiating the mesh formation. The mesh formation is 
initiated by the gateway upon user activation and terminated by the gateway when all possible 
devices join the network or when terminated by the user.
To form a mesh network, ensure that the gateway is powered on and contains a profile. (Refer to 
Section 2.5 on page 12 for information on how the gateway indicates its status). Activate the “Mesh 
Formation” magnet sensor on the gateway. Refer to Figure 2.2 for sensor location.
The gateway will then transition to the mesh formation mode and establish communication with all 
the devices containing a common profile. The blink pattern on the gateway indicates that it is in 
mesh formation mode. At this stage, both the LEDs on the gateway will blink twice every 7 sec-
onds. 
The first blink is green and the second blink is red when the gateway is acting as a profile 
distributor and forming the mesh. 
The first blink is green and the second blink is yellow when the gateway is only forming the 
mesh. 
Mesh formation typically takes one minute for each device in the mesh. Mesh formation automati-
cally terminates 10 minutes after the last device joins the mesh. Mesh formation can be terminated 
manually by the user by again activating the mesh formation magnetic sensor. 
Once the mesh formation is complete, the network automatically transitions to restructure the 
mesh. For operating instructions, refer to Section 2.9, “Operations”.
2.8.2  Configuration and Programming Using SWIFT Tools
Assign a Profile
To assign a profile to the gateway using SWIFT Tools:
1. Connect the W-USB dongle device to your laptop.  For more information on the USB dongle, 
2. Launch SWIFT Tools.  Refer to Appendix A for more information.
3. From the Home Screen, select the Create Mesh Network function.
4. Create a new profile or Import an existing profile as required.
5. Select and open the profile to be assigned to the gateway from the Name drop-down box in the 
Profile section.     
6. Power on the gateway within approximately 20 feet of the laptop running SWIFT Tools.
7. Ensure that the Scan On selection box in the Communicator Window is checked.
Figure 2.8  Creating or Importing a Profile
cr
e
at
e
pr
of
ile
.w
mf