Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
15
Configuration and Programming
WSK-WGI Wireless System Gateway
The gateway provides isolation of short circuits of the SLC in Class A (Style 6) installations. SLC connections are power-limited by the 
panel. +24VDC must be power-limited by the source.
2.8  Configuration and Programming
To successfully configure and/or program the gateway:
1.
Create a profile. A profile binds a gateway and the devices in a mesh network together. The profile will contain a mesh ID that is 
used when forming the associations. All devices, including the gateway, require a common profile.
2.
Distribute the profile. Distribute the profile to every device that will be a part of the mesh. This will enable all the devices that have 
that profile to form associative links when the mesh is formed.
3.
Form the mesh. The mesh cannot be formed until the profile is assigned to the gateway and distributed to its devices. 
These steps may be performed with or without using SWIFT Tools.
2.8.1  Configuration and Programming Without Using SWIFT Tools
This section explains the configuration of the gateway using only a magnet and a screw driver. For configuration instructions using 
SWIFT Tools, refer to Section 2.8.2. 
There are two ways to provide a gateway with a profile without using SWIFT Tools.
Create a new profile using the gateway.
Assign a previously created profile to the gateway using a distributor.
Create a New Profile
To create a unique profile in the gateway without using SWIFT Tools: 
1.
Start with the gateway powered off. The profile creation process is performed during start-up. 
2.
Power on the gateway using SLC power or external +24V. Refer to Sections 2.7.3 and 2.7.4 for more information.
3.
Ensure that the gateway is in the factory default state. If the gateway is in the factory default state, both the LEDs on the gateway 
will double blink red every second for ten seconds. If the LEDs are yellow, refer to “Remove a Profile” on page 16.
4.
Activate either magnetic sensor with a magnet within ten seconds of starting up the gateway while the double red blink is active on 
the gateway. Refer to Section 2.4, “Magnet Sensors” for further information on activating magnetic sensors. The LED next to the 
magnetic sensor emits a red light for one second when it is activated. If the ten second window is missed, power down the gateway 
and repeat the process starting at step 1.
A profile has been created successfully; the LEDs on the gateway will light green and stay on steady for ten seconds. The profile has 
been created containing a mesh ID and a default password. The default password is ‘12345678’ and is needed if the gateway is locked by 
the FACP and later accessed by SWIFT Tools.
+
+
-
-
+
-
Figure 2.7  Wiring Connections: WSK-WGI Powered by an External, Regulated +24VDC Source
SLC in from FACP/device
External +24VDC Power
SLC out to next device (Class B)
or SLC return to FACP (Class A)
2.
6.w
m
f