Code, Section IV or CSA B51, as applicable.  Select a relief valve with 
a discharge NOT less than the boiler input, and a pressure rating NOT 
exceeding the working pressure of any component in the system.
A. O. Smith supplies a 125 psi relief valve for hot water supply systems 
and 50 psi relief valve for space heating application. 
An ASME rated temperature and pressure relief valve must be installed 
on each and every water storage tank in a hot water supply system.
The storage tank temperature and pressure (T & P) relief valve must 
comply with the applicable contruction provisions of the Standard 
for Relief valves and  Automatic Gas Shutoff Devices for Hot Water 
Supply Systems, Z21.22 - CSA 4.4. The T & P valve must be of the 
automatic reset type and not embody a single-use type of fusible 
plug, cartridge or linkage.
The T & P relief valve should have a maximum temperature rating 
of  100°C  (210°F),  a  pressure  rating  NOT  exceeding  the  lowest 
rated working pressure of any system component, and a discharge 
capacity  exceeding  the  total  input  of  the  water  boilers  supplying 
water to the storage tank.
Locate the T & P relief valve (a) in the top of the storage tank or (b) 
in the side of the tank on centerline within upper 6 inches from the 
top of the tank. See Figures 28 to 33, Pages 34 to 38. Tapping shall 
be threaded in accordance with the latest version of the Standard for 
Pipe Threads, General Purpose (inch), ANSI/ASME B.120.1.
Mark  location  with  a  class  III  Label.  See ANSI  Z21.10.1,  Part  1, 
Marking, See CAN/CSA B149.
TANK TEMPERATURE CONTROL
The water temperature in the storage tank is controlled by the Tank 
Temperature Control. The sensing element is mounted inside the 
hot water storage tank.
 
DANGER
HOT  WATER TEMPERATURES  REQUIRED  FOR AUTOMATIC 
DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS 
RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH. 
THE  TEMPERATURE AT  WHICH  INJURY  OCCURS  VARIES 
WITH  THE  PERSON’S AGE AND  TIME  OF  EXPOSURE.  THE 
SLOWER RESPONSE TIME OF CHILDREN, AGED OR DISABLED 
PERSONS INCREASES THE HAZARDS TO THEM. NEVER ALLOW 
SMALL CHILDREN TO USE A HOT WATER TAP, OR TO DRAW 
THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR DISABLED 
PERSON UNATTENDED IN A BATHTUB OR SHOWER.
The tank temperature control is adjustable from 100°F (37.7°C) to 
220°F (104.4°C). It is recommended that lower water temperatures 
be used to avoid the risk of scalding. It is further recommended, in all 
cases, that the water temperature be set for the lowest temperature 
which satisfies the user’s hot water needs. This will also provide the 
most energy efficient operation of the water heater and minimize 
scale formation.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA WHERE 
THE  GENERAL  PUBLIC  DOES  NOT  HAVE ACCESS  TO  SET 
TEMPERATURES.  SETTING THE  WATER TEMPERATURE AT 
120°F (49°C) WILL REDUCE THE RISK OF SCALDS. Some states or 
provinces require settings at specific lower temperatures. Below you 
will find listed the approximate time-to-burn relationship for normal 
adult skin. Valves for reducing point-of-use temperature by mixing 
cold  and  hot  water  are  available. Also  available  are  inexpensive 
devices that attach to faucets to limit hot water temperatures. Contact 
a licensed plumber or the local plumbing authority.