This is a typical first Generator Parameter page for a 
single phase system. 
LINE 1:  Phase titles for the voltage and current 
– voltage title/current title.
LINE 2:  Line-to-Line voltage for AB and Line-to-
Neutral voltage for A and B in Volts RMS.
LINE 3:  Neutral current and Line currents in Amps 
RMS. 
LINE 4:  Generator frequency in Hz followed by the 
“More” field to allow page selection.
Press the “ENTER” button.
This is a typical second Generator Parameter page for 
a three phase system. 
LINE 1:  Total system real power in kW.
LINE 2:  Total system power factor.
LINE 3:  Percentage of the system rated power being 
used.
LINE 4:  The “More” field to allow page selection.
This is a typical second Generator Parameter page for 
a single phase system. 
LINE 1:  Phase titles for the power and power factor 
– Total, A-Neutral, B-Neutral.
LINE 2:  Real power in kW – Total system, A-Neutral, 
B-Neutral.
LINE 3:  Power Factor – Total system, A-Neutral, B-
Neutral.
LINE 4:  The “More” field to allow page selection.
Press the “ENTER” button.
This is a typical third Generator Parameters page. It 
graphically displays the percent of i
2
t thermal limit 
currently attained. If the limit is exceeded, an alarm 
will be set and the generator will shutdown to protect 
the alternator. This display will then show % Temp 
>Over Limit<”. GenLink can provide more informa-
tion regarding actual limits exceeded. This page is 
disabled if the i
2
t  function is disabled.
DIAGNOSTICS
There are six System Diagnostic pages. They are digi-
tal inputs page, digital outputs page, two analog input 
pages, RS-232 communications status page, and RS-
485 communications status page.
Do the following to view the diagnostics pages:
Press the “MENU” button.
Press the 
 button twice and the  button.
Press the “ENTER” button.
  
19
General Information
H-100 Control Panel Technical Manual