GAS KETTLES 
— 7 — 
 
 
Gas Connection Data 
 
 
FLEXIBLE GAS CONNECTORS BTU/hr. FLOW CAPACITY 
1, 2
 
 
LENGTH 
3
 
LENGTH 
3
 
 
End Fittings - (1) Quick Disconnect 
& (1) Threaded 
 
End Fittings - Both Threaded 
ID 
36" 
48" 
60" 
72" 
36" 
48" 
60" 
72" 
1
/
2
" 
77,000 
68,000 
60,000 
55,000 
120,000 
106,000 
93,000 
86,000 
3
/
4
" 
218,000 
180,000 
158,000 
139,000 
256,000 
225,000 
198,000 
175,000 
1" 
379,000 
334,000 
294,000 
279,000 
512,000 
451,000 
397,000 
350,000 
1
1
/
4
"  615,000 
541,000 
476,000 
419,000 
946,000 
833,000 
733,000 
645,000 
1.   Flow rating BTU/hr. 0.64 SP. GR @ 0.5 inch W.C. pressure drop. 
 
2.   BTU/hr. flow capacities are based on Dormont Mfg. Co. Supr-Safe gas line connectors and are 
provided for reference. Additional quick disconnect fittings, swivels, or manual shut off valves will 
reduce the BTU/hr. flow capacities listed in this table. If other flexible gas connectors are used, 
check the manufacturer’s specifications for BTU/hr. flow capacities. Supr-Safe is a registered 
trademark of the Dormont Manufacturing Company. 
 
3.   The maximum length for a flexible gas connector is 72" per National Fuel Code standards. 
 
 
BLACK IRON PIPE BTU/hr. FLOW CAPACITY 
1, 2, 3
 
Natural Gas 
Nominal Inside Diameter of Pipe 
Pipe Length 
1
/
2
" 
3
/
4
" 
1" 
1
1
/
4
" 
1
1
/
2
" 
2" 
15' 
76,000 
172,000 
345,000 
750,000 
1,220,000 
2,480,000 
30' 
52,000 
120,000 
241,000 
535,000 
850,000 
1,780,000 
45' 
43,000 
99,000 
199,000 
435,000 
700,000 
1,475,000 
60' 
38,000 
86,000 
173,000 
380,000 
610,000 
1,290,000 
75' 
 
77,000 
155,000 
345,000 
545,000 
1,120,000 
90' 
 
70,000 
141,000 
310,000 
490,000 
1,000,000 
1.   Flow rating BTU/hr. 0.64 SP. GR @ 0.3 inch W.C. pressure drop. 
 
2.   BTU/hr. flow capacities are based on Schedule 40 pipe, include a tolerance for pressure losses 
in gas piping systems are provided for reference. 
 
3.   Count each 90° elbow as 3' of gas pipe for the purpose of calculating total pipe length. 
 
TESTING THE GAS SUPPLY SYSTEM 
 
When gas supply pressure exceeds 
1
/
psig (3.45 kPa), the kettle and its individual shutoff valve must 
be disconnected from the gas supply piping system. 
 
When gas supply pressure is 
1
/
2  
psig (3.45 kPa) or less, the kettle should be isolated from the gas 
supply system by closing its individual manual shutoff valve.