GAS KETTLES 
— 8 — 
 
 
GAS AND ALTITUDE CONVERSION 
The  kettle  can  be  field  converted  to propane 
gas or for operation at altitudes above 2000ft 
elevation.A manometer that reads in 1/100" WC 
and portable combustion analyzer are required. 
Natural gas to Propane gas conversion: 
1. Remo ve   the   r ig ht   side   co ntrols 
compartment side panel. 
2. Locate the gas combination valve located 
in the bottom of the controls compartment. 
3. Turn S1 screw located  right of manifold 
pressure  port  (Fig.  1)  clockwise  to 
completely  close  position.  Then  turn 
counter clockwise 10 turns. 
4. Pressure at inlet port should be between 
11" and 13" WC. 
5. Turn the unit on. 
6. Fill the unit half way with cold water. 
7. Run  the  unit  for ½  hour  to  burn  off any 
residue in combustion chamber. 
8.  Using  the  combustion  analyzer  check 
the flue gases. If the analyzer reads Co 
Free  Air  the  combustion  gases  should 
not  exceed  0.04  %  or  400  PPM. If  the 
analyzer does not read Co Free verify the 
 
 
Fig. 1 
Co reading is below 100 PPM. If the reading is above, verify your settings and retest.  If readings 
are still high, call tech support at the number located on the front of this manual. 
9. Attach the conversion data plate located in the bottom of the controls compartment with rivets 
provided. The plate is to be mounted next to the kettle’s factory data plate. 
10. Replace the controls compartment panel. 
Propane gas to Natural gas conversion: 
1. Remove the right side controls compartment side panel. 
2. Locate the gas combination valve located in the bottom of the controls compartment. 
3. Turn  S1  screw  located  right  of  manifold  pressure  port  (Fig.  1)  clockwise  to  completely  close 
position. Then turn counter clockwise 16 turns. 
4. Pressure at inlet port should be between 5" and 10.5" WC. 
5. Turn the unit on. 
6. Fill the unit half way with cold water. 
7. Run the unit for ½ hour to burn off any residue in combustion chamber. 
8. Using  the  combustion  analyzer  check  the  flue  gases.  If  the  analyzer  reads  Co  Free  Air  the 
combustion gases should not exceed 0.04 % or 400 PPM. If the analyzer does not read Co Free 
verify the Co reading is below 100 PPM. If the reading is above verify your settings and retest. 
If readings are still high call tech support at the number located on the front of this manual. 
9. Attach the conversion data plate located in the bottom of the controls compartment with rivets 
provided. The plate is to be mounted next to the kettle’s factory data plate. 
10. Replace the controls compartment panel.